Fault warning system SM-10.. |
|
|
 |
SM-10
Built-in fault warning system
with LED fault display.
Designed for monitoring the function of technical control and regulation systems.
-
10 independent fault inputs
-
Collective fault signal contact
-
Various function variants
-
Option "-L" with wire break protection (see page 3)
-
Option "-5S" with time-delayed fault signal (see page 3)
Description of features |
[back]
Connection
Technical data
Housing
Infofolder
Operating Instructions
SM-10z
SM-10b
SM-10m
SM-10v
SM-10q
|
| |
Version SM-10z*
 |
- 10 independent fault inputs
- Collective fault contact with collective fault LED
- Power failure detection
|
|
Version SM-10b*
 |
- 10 independent fault inputs
- Collective fault contact with collective fault LED
- Power-on RESET
|
|
Version SM-10m*
 |
- 10 independent fault inputs
- Collective fault contact with collective fault LED
- AUTO RESET
|
|
VersionSM-10v*
 |
- 10 independent fault inputs
- Collective fault contact with collective fault LED
- Power failure detection
- Fault memory
|
|
Version SM-10q*
 |
- 10 independent fault inputs
- Collective fault contact with collective fault LED
- Fault memory
- Power-on RESET
|
|
| |
Option "-L":
Input signals are processed LOW-ACTIV, which means: In operating mode, voltage must be applied to the fault inputs. An fault is then displayed when the voltage drops.
Option "-5S":
Incoming faults (whether HIGH-ACTIV or LOW-ACTIV) are reported with the specified time delay. This means that short-term faults are ignored. |
|
| |
Connection |
Customised designs
We can quickly and cost-effectively implement special customer requests with regard to special functions or modified front layouts (e.g. with your company logo). |
 |
|
|
| |
Technical data |
| |
Operating voltage |
230V AC +/-10%, 50/60 Hz
115V AC +/-10%, 50/60 Hz
24V AC +/-10%, 50/60 Hz
24V DC
24V UC |
Fault signal inputs |
10 (via optocoupler) |
Display |
5mm LED per fault input
+ mains control LED
+ collective fault LED |
Relay contact |
1 changeover contact
potential-free |
Max. switching current |
8 A AC1 |
Max. switching voltage |
250 V ~ |
Housing
- Front dimensions
- Panel cut-out
- Installation depth |
48 x 96 mm
42 x 90 mm
88 mm
|
Protection class |
IP 64 (front of housing) |
Connection |
pluggable terminal strips |
Ambient temperature
- Operating temperature
- Storage temperature
- Max. humidity |
0° to +50°C
-20° to +70°C
75% (no condensation)
|
|
|