Fault warning system - SM-10..

 |
Fault warning system in front panel housing.
|
|
For monitoring the functions of technical control or regulation systems.
|
- 10 independent fault inputs
- Collective fault contact
- different function variants
- broken wire fuse optional
- fault indication with time lag optional
(Description of the features) |
| |
Version SM-10z*

|
- 10 independent fault inputs
- Collective fault contact via LED
- Loss-of-voltage recognition
|
|
Version SM-10b*

|
- 10 independent fault inputs
- Collective fault contact via LED
- Switch-on reset
|
|
Version SM-10m*

|
- 10 independent fault inputs
- Collective fault contact via LED
- AUTO-RESET
|
|
Version SM-10v*

|
- 10 independent fault inputs
- Collective fault contact via LED
- Loss-of-voltage recognition
- Fault memory
|
|
Version SM-10q*

|
- 10 independent fault inputs
- Collective fault contact via LED
- Fault memory
- Switch-on reset
|
|
Option "-L":
Input signals are processed LOW-ACTIVELY, i.e. in operating status the fault inputs must be under voltage. Faults are then indicated if voltage is lost.
Option "-5S":
Incoming faults (regardless of whether HIGH- or LOW-ACTIVE) are indicated with a delay corresponding to the set number of seconds.
Faults of a short duration are ignored.
|
|
| |
Connection diagram |
|
Tailor-made models
Customers’ individual wishes in terms of special functions or different frontal layouts with company logo can be fulfilled quickly and economically.
We will also be pleased to inform you about existing variants of basic devices or the possibility of tailor-made adaptations to suit your specific needs. |

|
|
| |
Technical data |
|
| |
Operating voltage |
230V AC +/-10%, 50/60 Hz
115V AC +/-10%, 50/60 Hz
24V AC +/-10%, 50/60 Hz
24V DC
24V UC |
Fault inputs |
10 via opto coupler |
Display |
5 mm LED for each falt input
+ mains-check LED
+ collective fault LED |
Relay contact |
1 voltage-free two-way contact |
max. switching current |
8 A AC1 |
max. switching voltage |
250 V ~ |
| Housing
- front panel
- front-panel cut-out
- installation depth |
48 x 96 mm
42 x 90 mm
88 mm
|
Protection (housing front) |
IP 64 |
Connection |
screw terminals |
Ambient temperature
- operation temperature
- storage temperature
- max. humidity |
0° to +50°C
-20° to +70°C
75% (no condensation)
|
|