2-step temperature reglulator with integr. fault warning system - MPR-SMK

Temperature regulator with built-in fault indicator with 10 fault input ports. Housing front 48 x 96 mm

For controlling heating and refrigeration operations in technical systems, with simultaneous monitoring of functions.

Multiple programming options.

Can be ordered with 1-3 switching contacts to control compressors, heaters, alarms etc.

 

Temperature regulator unit:

  • Easy operation via three work levels
  • Automatic parameter storage without data loss when a power-cut occurs
  • Target temperature and upper/lower hysteresis limit freely adjustable
  • Alarm in the event of sensor short-circuit/sensor fault (adjustable relay switching state in event of fault)
  • Separately adjustable minimum action time and minimum pause time for output relay
  • adjustable high or low temperature alarm

 

Fault warning unit:

  • 10 independent fault inputs programable as 'high' or 'low' inputs
  • Collective fault contact via LED
  • Different RESET versions programable
 

 

Connection diagram

Tailor-made models

Customers’ individual wishes in terms of special functions or different frontal layouts with company logo can be fulfilled quickly and economically.

We will also be pleased to inform you about existing variants of basic devices or the possibility of tailor-made adaptations to suit your specific needs.

 


  Technical data
 

Operating voltage

230V AC +/-10%, 50/60 Hz
115V AC +/-10%, 50/60 Hz
24V AC +/-10%, 50/60 Hz
24V DC
24V UC

Housing
- front panel
- front-panel cut-out
- installation depth


48 x 96 mm
42 x 90 mm
88 mm

Protection (housing front)

IP 64

Connection

screw terminals

Ambient temperature
- operation temperature
- storage temperature
- max. humidity


0° to +50°C
-20° to +70°C
75% (no condensation)

Display

13 mm LED-Display, 3 digits

Display range

-99 to 999

 

Temperature regulator unit:

Relay contact

1..3 two-way-contacts, voltage-free
depending on model

max. switching current

10 A AC1

max. switching voltage

250 V ~

Usable sensor types

KTY 81-210 or PT 100

Measurement range
- KTY 81-210
- PT 100 - 2 leads
- PT 100 - 3 leads


-50° to +150°C
-99° to +400°C
-99° to +400°C

Control type

two-step regulator

Hysteresis

0,1 K to 99,9 K freely adjustable

Operation mode

heating/cooling interchangeable

 

Fault warning unit:

Fault inputs

10 via opto coupler

Relay contact

1 two-way-contact voltage-free

max. switching current

10 A AC1

max. switching voltage

250 V ~